Capacitance & Rf Admittance Type Level Transmitter & Switches
A capacitance is formed between the probe and the vessel wall .As the level of the measuring medium rises or falls capacitance between the probe and vessel wall changes proportionately. A high frequency sine wave is applied between the probe and tank wall. A change of medium level will induce a change in the current of the applied sine wave. From when the capacitance in the vessel increase, impedance will decrease and current will increase and vice-versa. (Z=Resistance, C=Capacitance, F= Frequency)


Head mounted electronics converts the capacitance variation to 4-20mA signal for long distance transmission. It is provided with trimpots for SPAN and ZERO adjustments. With no moving parts it is free from wear and tear, rugged and robust in construction. No dead zone like float based instruments.
It must be ensured that the probe is parallel to the tank wall throughout it's length.
Technical Specification
RF admittance/capacitance type 3 wire Level transmitter Model (CLT-1) with non insulated probes for non-conductive liquids or PTFE Teflon insulated probes for conductive liquids.
Frequency of operation | 5 to15kHz. |
---|---|
Probe Material | Stainless Steel / Teflon insulated 10/12/16 mm rod upto Max 3 Metre length |
Process connection | 3/4",1",1.1/2" BSP(M) or 1 "ASA 150 lbs flanged but thickness 12mm (or as per customer specification) |
Power supply | 24VDC |
Output | 4 to 20 mA.(non-isolated) |
Span & Zero adjustment | Trim pots |
Max.Working Pressure | 10kg/sq.cm |
Max.Working Temp. | 150deg.C |
Accuracy | ±0.5%, ±1% or ±2% |
Enclosure | Cast aluminium weather proof with PG9 cable gland or Flame proof (IS2148-2004,Gr II A and B gases) |
Cable Size | 3 core, 0.75 sq.mm screened PVC cable. |
RF Admittance Type Level Switches :
Model (RF-LS1) , RF-Admittance Type Level Switch The system is a DRIVEN SHIELD, COAT GUARD single point level switch. The electronics control unit is integral to the probe. Fail safe logic is field selectable.

Housing | Cast Aluminum weather proof |
---|---|
Cable Entry | 2x 16mm |
Mains | 230VAC / 24VDC |
Output | 2 nos potential free C/O contacts rated at 5 amps, 230 VAC resistive |
Probe | INTEGRAL |
Mounting | 1.1/2"BSP(m) threaded |
Sensing | Stainless Steel |
Insulations | PTFE |
Probe Length | 250mm |
Capacitance Type Level Swtiches :
Capacitance Type Level Switch Model (CLS-1)

Housing | Cast Aluminum weather proof |
---|---|
Cable Entry | 2x PG7 |
Mains | 24VDC |
Output | 2 nos potential free C/O contacts rated at 5 amps, 230 VAC resistive |
Probe | SS304 / SS316 Non insulated or PTFE insulated |
Mounting | 1/2" or 3/4" BSP(M) or 1 "ASA 150 lbs flanged but thickness 12mm |
Probe Length | 100mm as Standard. |
Max. Working Pressure | 4 kg/sq.cm |
Max. Working Temp. | 150 deg C |